Armoire débrochable basse tension GCK pour appareillage de commutation

Le tableau de distribution GCK à basse tension débrochable est largement utilisé dans les centrales électriques, les aciéries métallurgiques, l’industrie pétrochimique, l’industrie légère et textile, les ports et terminaux, les bâtiments et hôtels et autres lieux en tant que système d’alimentation électrique triphasé à quatre ou cinq fils, tension 380 V, 660 V, fréquence 50 Hz, courant nominal de 5000 A et moins pour la distribution d’énergie et la commande centralisée des moteurs.

GCK low-voltage withdrawable switchgear is widely used in power plants, metallurgical steel rolling, petrochemical industry, light industry and textiles, ports and terminals, buildings and hotels and other places as AC three-phase four-wire or five-wire system, voltage 380V, 660V, frequency of 50Hz, rated current of 5000A and below power supply system for power distribution and motor centralized control.

The GCK is type-tested is assembled as a low-voltage switchgear designed to meet the following standards:
National Standard GB7251.1-2005 « Low-voltage Switchgear »
Standard IEC60439.1-1992 « Low-voltage switchgear and control equipment »

  • The ambient air temperature is not higher than +40°C and not lower than -5°C, and the average temperature is not higher than +35°C within 24 hours;
  • The relative temperature is not more than 50% at +40°C, and a higher relative temperature is allowed at lower temperature, such as 90% at +20°C;
  • Clean air, no corrosive and explosive gases, no conductive and insulation-destroying dust:
  • When there is no shaking and shock vibration, the inclination should not be greater than 5 degrees for vertical installation;
  • The altitude does not exceed 2000 meters;
  • The switch cabinet is suitable for transportation and storage at the following temperatures: -25°C to +55°C, and not more than +70°C in a short time (no more than 24 hours);
  • If the user cannot meet the above conditions, he or she shall negotiate with the manufacturer.
  • Rated insulation voltage: 660V/1000V
  • Rated working voltage: 400V/660V
  • Rated working voltage of auxiliary circuit: AC 380V, 220V, DC 110V, 220V
  • Bus rated current: 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A
  • Rated short-time withstand current of bus: 50kA, 80kA (effective value) for 1 second
  • Rated peak withstand current of bus: 105kA/0.1s, 140kA/0.1s, 176kA/0.1s
  • Branch bus rated current: 630A, 1000A, 1250A, 1600A
  • Rated short-time withstand current of branch bus: 30kA, 50kA (effective value) for 1 second
  • Rated peak withstand current of branch bus: 63kA, 105kA/0.1s
  • Enclosure protection level: IP30, IP40
  • Bus setting: three-phase four-wire system, three-phase five-wire system
  • Operation mode: local, remote, automatic